ENC-GR500EX
- Cooling power:500W
- Voltage:Single-phase AC 200~240V
- Installation method:Ceiling-mount
- Dimensions:H374xW550xD270mm
- Weight:26kg
Specifications Installing the dimensional
ENC-GR500EX | (50Hz) | ||||||||
Model | ENC-GR500EX | ||||||||
Performance | Cooling capacity (W) | 2100/2400 | |||||||
Settingtemperature range (℃) | 25~45 | ||||||||
Use Area temperature (℃) | 20~55 | ||||||||
Use Area humidity (%RH) | 10~85(No condensation) | ||||||||
External | External dimensions (H×W×D)(mm) | 347 × 550 × 270 | |||||||
Weight (kg) | 26 | ||||||||
Coating color | Munsell 5Y 7/1 Equivalent color of light beige | ||||||||
Power Supply | Rated voltage (V) | Single-phase AC200~240V | |||||||
Consumption current | Rating (A) | 1.8/1.6 | |||||||
MAX (A) | 2.3/2.1 | ||||||||
Power consumption | Rating (W) | 250 | |||||||
MAX (W) | 346 | ||||||||
Dust & Water protection grade | IP54 Equivalent to internal circulation toute | ||||||||
Coolant | |||||||||
Noise (dB) | Approx.64 | ||||||||
External Output | Alarm output(a contact:No-voitage resistive load 250V 2A) | ||||||||
Display | Panel internal temperature/Eror code LED,RUN LED | ||||||||
Environmental Response | RoHS |
Notes:Cooling capacity: the related value when the ambient temperature is 35℃ and the panel intelal temperature is 35℃. (Measurement condition: simple indoor side air enthalpy testing method based on JIS-C-9612)
Rated value:35℃ ambient temperature,ambient humidity RH 40%.
MAX value:Ambient temperature at the time of use is the maximum allowable ambient temperature,when ambient humidity at the time of use is RH 40%.
Please read the instruction carefully before useing and use it correctly.